Surge Capacity
20KA - 40KA
🛡️
Protection Class
Class C
⚙️
Installation
Standard Rail 35mm
Technical Specifications
| TYPE |
HSP1-C 20KA-40KA Surge protector |
| Protection Class |
C |
| Working Voltage Un(AC) |
220V |
320V |
320V |
420V |
| Max. continuous operating voltage Uc(AC) |
275V |
380V |
420V |
480V |
| Volt protection level Up(V~)KV |
≤1.0 |
≤1.2 |
≤1.8 |
≤2.8 |
| Nominal Discharge Current (8/20μs) (In) |
20KA |
| Max. Discharge Current (8/20μs) (Imax.) |
40KA |
| Voltage Protection Level( Up) |
≤1.5KV |
| Test standard |
IEC61643.1, GB18802.1 |
| Response Time |
< 25ns |
| Leakage current |
≤20μA |
| Working Environment |
Temperature -40°C +85°C; Relative humidity <95% |
| Max connection line |
35mm² hard wire / 35mm² strand wire copper line |
| Recommended connection line |
16mm² hard wire / 25mm² strand wire copper line |
| indicate deterioration |
Green: Normal; Red: Deterioration |
| Protection Mode |
L-PE, N-PE (2P) |
| Material of Outer Shell |
Flame retardant materials |
| installation |
Standard rail 35mm |
| Weight |
0.56kg/4 pole |
| Material of outer covering |
Burning proof nylon |
Product Gallery
Frequently Asked Questions
What is the primary function of the HSP1-C surge protector?
The HSP1-C surge protector is designed to protect household and industrial electrical systems from transient overvoltages and electrical surges, preventing damage to connected appliances and sensitive electronics.
What do Nominal (In) and Max (Imax) discharge currents mean?
The Nominal Discharge Current (In = 20KA) is the peak value of a surge current the device can handle repeatedly. The Max Discharge Current (Imax = 40KA) is the maximum peak current the device can discharge safely a single time without failure.
How do I know if the surge protector needs replacement?
The device features a clear visual indicator on the front panel. When it displays Green, the protector is in normal operation. If the indicator turns Red, it means the device has deteriorated and must be replaced immediately.
What are the recommended wiring sizes for installation?
For optimal safety, we recommend using a 16mm² hard wire or a 25mm² strand copper wire. The terminals can support up to a maximum connection line of 35mm² hard or stranded copper wires.
What is the response speed of this surge protection device?
The HSP1-C operates with an ultra-fast response time of less than 25 nanoseconds (< 25ns), ensuring that overvoltages are quickly suppressed before they reach downstream equipment.
What type of mounting does the HSP1-C require?
It is designed for standard 35mm rail mounting, making it easily compatible with standard electrical distribution boxes and consumer units.